PART IV
DETAILED SPECIFICATION
Vista de página 0
1 2 3 4 5 6 ... 22 23

Resumo do Conteúdo

Página 1 - DETAILED SPECIFICATION

PART IV DETAILED SPECIFICATION

Página 2

9 the SLC loop and can be placed up to 10,000 feet from the control or 5815XL SLC loop module. 2.1.8 Annunciators A. The main control shall have

Página 3

10 2.1.12 Distributed Power Modules A. The contractor shall supply (where required) a power module, Model 5895XL, compatible with the 5820XLRVS fi

Página 4

11 external modems for remote programming and diagnostics shall be accepted. C. Provide a dual line digital communicator with battery back-up. Uni

Página 5

12 D. A bypass mode shall allow for any point or NAC circuit to be bypassed without affecting the operation of the total fire alarm system. 2.1.18

Página 6

13 shall contain a code that shall block unauthorized persons from accessing the panel via direct connection or over the phone lines. 2.1.22 Facili

Página 7

14 key at the main or remote annunciators. When silenced, this shall not prevent the resounding of subsequent events if another event shall occur.

Página 8

15 SECTION THREE: SYSTEM COMPONENTS 3.0 Control Unit 3.1 System Cabinet Mounting A. The system cabinet shall be red and may be either surface

Página 9

16 SECTION FOUR: ACCESSORY COMPONENTS 4.1 The FACP shall support the following devices on the SBUS: 5815XL Signaling Line Circuit Expander (S

Página 10

17 M02-04-01 Detector Test Magnet M02-09-01 Telescoping Test Magnet SK-Pull-SA Addressable Single Action Pull Station SK-Pull-DA Addressable Dual

Página 11

18 B. The 5895XL shall support 6 amps of 24 volt DC power, with 6 Flexput circuits, rated at 3amps each. Two additional 5815XL SLC loop expanders s

Página 12

1 PART IV – DETAILED SPECIFICATIONS SECTION ONE: GENERAL 1.1 Scope A. This specification document provides the requirements for the installa

Página 13

19 perform a sensitivity test of the detector without the need of generating smoke. The test method shall simulate the effects of products of combust

Página 14

20 SECTION FIVE: WIRING 5.1 Installer’s Responsibilities A. The installer shall coordinate the installation of the fire alarm equipment. B. Al

Página 15

21 SECTION SIX: WARRANTY AND FINAL TEST 6.1 General A. The contractor shall warranty all materials, installation and workmanship for Two (2) yea

Página 16

22 A. Before the installation shall be considered completed and acceptable by the owner, a test of the system shall be performed as follows: 1.

Página 17

2 on the drawings. The system shall include but not be limited to all control panels, power supplies, initiating devices, audible and visual notifica

Página 18

3 UL 2572 Control and Communication Units for Mass Notification Systems 1.3.6 Americans with Disabilities Act (ADA) A. All visual Notification a

Página 19

4 the shop drawings to be furnished under this contract shall be clearly marked in the specification sheets. 3. Supplier’s qualifications shall

Página 20

5 1.4.4 Products A. This life safety system specification shall be conformed to in its entirety to ensure that the installed and programmed life

Página 21

6 SECTION TWO: SPECIFICATIONS 2.1 General 2.1.1 Control Panel A. Control Panel with Emergency Voice System 1. The fire alarm control pan

Página 22

7 7. The FACP shall have a built-in UL approved digital communicator which shall allow local and remote up/downloading of system operating options,

Página 23

8 separate from the SLC circuit. The SLC shall be capable of functioning in a Class A or Class B configuration. 2.1.4 SLC Loop Devices A. Device