Programming Overview
151295 6-3
5. When the message "Configuring System Done" displays, press any key to continue.
6. Select one of the following options from the menu that displays.
- Review System Press if you need to review the JumpStart configuration.
- Repeat JumpStart Press if you need to rerun JumpStart for any reason.
- Accept Configuration 1. If you are ready to make the JumpStart configuration permanent, select .
2. The system will ask you if the installation contains duct detectors. If there are
none, select for No and skip to Step 8. If the system contains duct detec-
tors, select for Yes and continue with Step 3.
3. From the list, select the SLC device that contains the duct detectors.
4. The first photoelectric detector on the system will display. Select for
DUCT and for NonDUCT.
5. Press to select the next detector. Select for DUCT and for Non-
DUCT. Continue until all duct detectors have been selected. (Note: You can
move backwards through the list with .)
6. When you reach the last detector on this device, press .
7. The system will ask you if there are more duct detectors in the system. If there
are, select for Yes and repeat from Step 3. If there are no more duct
detectors, select for No and continue with Step 8.
8. The system will restart in 10 seconds, or press to restart immediately. Do
not select for System Diagnostics (This feature is for testing at the fac-
tory.)
9. After the system resets, it will use the new JumpStart configuration.
- Enter Programming To go directly to Program Mode to configure any devices, press . The
Programming Menu appears and you can begin programming.